Scanning under load
Thermal scanning is carried out while the panel is under its normal operating load; a scan performed without load will not reveal the heating effect of a loose connection.
What's Included
- Thermal scanning of panels and connection points
- Temperature measurement under load
- Comparative analysis against neighboring points
- Findings reported in order of criticality
- Thermal and visual image documentation
- Predictive maintenance prioritization
Cover-open scanning
Provides a clearer image, and is carried out with proper protective equipment and a work permit because of the risk of working on live parts.
Cover-closed scanning
Delivers results without risk on panels fitted with an infrared viewing window.
A temperature difference above 15 degrees Celsius compared with neighboring connection points is treated as an urgent priority.
Frequently Asked Questions
Can thermal scanning be done without stopping production?
Yes, the scan is carried out while the panel is under its normal operating load, so the production flow is not affected.
Which temperature difference calls for urgent action?
Deviations that exceed a certain threshold compared with neighboring connection points are flagged as urgent, and the threshold varies with the load type.
In what format is the scan result delivered?
It is delivered as a digital report combining thermal images and real photographs, prepared in order of criticality.
Request a Quote for This Service
Give us a brief outline of your project and our team will get in touch.
+90 532 312 00 59 Get a Quote